User Manual
5-12
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
$AAM
Name Read Module Name command
Description The command requests t he analog input module at addr ess
AA to return its name.
Syntax $AAM (cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character he xadecimal
address of the analog input module that you want to
interrogate.
M is the Read Module Name command.
(cr) is the terminating character, carriage return (ODh).
Response !AA(Module Name)(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error, or if t he speci fied a ddress does not
exist.
! is a deli miter ch aracter indicatin g a valid co mmand was
received.
AA (range 00-FF) represents the 2-character he xadecimal
address of an analog input module.
(Module Name) is the name of the module at address AA.
(cr) is the terminating character, carriage return (ODh).