User Manual
5-10
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
$AA2
Example com mand: $452(cr)
response:
! 45050600(cr)
The command asks the analog input module at address 45h
to send its configuration data.
The analog input module at address 45h responds with an
input r ange of 2.5 vo lts, a b aud rate of 96 00 bps,
an
integration time of 50 ms (60 Hz), engineering units are the
currently co nfigured data format, and no c hecksum
function or checksum generation.