User Manual

Command Set
4-
22
ADAM 4000 Series User’s Manual
ADAM-4019+ Command Table
Command Syntax
Command Name
Command Description
Page
No.
%AANNTTCCFF
Configuration
Sets the address, baud rate, data
format, checksum status, and/or
integration time for a specified
analog input module
5
-
4
$AA2
Configuration
Status
Returns the configuration
parameters for the specified
analog input module
5
-
10
$AAF
Read Firmware
Version
Return the firmware version code
from the specified analog output
module
5
-
12
$AAM
Read Module
Name
Return the module name from the
specified analog output module
5
-
13
#AA
Analog Data In
Returns the input value from a
specified analog input module in
the currently configured data
format
5
-
14
#AAN
Read Analog Input
from Channel N
Returns the input value from a
specified channel of analog input
module in the currently configured
data format
5
-
16
$AA5VV
Enable/Disable
Channels for
Multiplexing
Enable or disable the individual
channels in an analog module
5
-
17
$AA6
Read Channel
Status
Get the enable/disable status of all
channels in an analog module
5
-
18
$AAB
Get
O
perating
S
tatus
Get the channel operating status
When
bit value is 0, it mean this channel is in
normal operating, when bit value is 1, it
mean this channel is opening wire
5
-
24
$AA3
CJC Status
Returns the value of the CJC
sensor for a specified analog input
module
5
-
25
$AA9SNNNN
CJC Offset
Calibration
Calibrates an a
nalog input module to
adjust for offset errors of its CJC
sensors
5
-
26
(Continued on following page)