User Manual

Chapter 4
Chapter 4 Command Set
4-19
ADAM-4018+ Command Table (Continued)
Command Syntax
Command Name
Command Description
Page No.
$AA1
Ci
Offset Calibration
Offset error calibrate of assignment
channel, User have to input the external
standard source for calibrating process
5
-
28
$AA7CiRrr
Input
R
ange
S
etting
Input range setting individually
5
-
29
$AA8
Ci
Read I
nput
Range
Get the input
range
of the assignment
channel
5
-
30
$AAXnnnn
Set
C
ommunication
WDT
Set communication
WDT
cycle
time from
0000 ~ 9999 (unit: 0.1 second. if value is
0000, the communication WDT function
will be disable)
5
-
31
$AAY
Get
C
ommunication
WDT Setting
Read the
cycle time
setting of
communication WDT
5
-
32
ADAM-4018+
Input range and external calibrating input source for each input type
Range
bcode(Hex)
Input Range
Max. Signal
Min Signal
Displayed
Resolution
0
6
+/
-
20 mA
+20.000
-
20.000
1uA
0
7
4
~20 mA
+
20
.000
+4
.000
1uA
14
Type J
Thermocouple
15
Type
K
Thermocouple
16
Type
T
Thermocouple
17
Type
E
Thermocouple
18
Type
R
Thermocouple
19
Type
S
Thermocouple
20
Type
B
Thermocouple