User Manual

Chapter 4
Chapter 4 Command Set
4-17
ADAM-4018 Command Table
Command Syntax
Command Name
Command Description
Page No.
%AANNTTCCFF
Configuration
Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analog input module
5
-
4
$AA2
Configura
tion Status
Return the configuration
parameters for the specified analog
input module
5
-
10
$AAF
Read Version
Return the firmware version code
from the specified analog input
module
5
-
12
$AAM
Read Module Name
Return the module name from the
specified analog input module
5
-
13
#AA
Read Analog Input
from all Channels
Return the input value from all
channels of the specified analog
module
5
-
14
#AAN
Read Analog Input
from Channel N
Return the input value from
channels number N of the
specified analog input module
5
-
16
$AA5VV
Enable/disable
Channels for
Multiplexing
Enables/disables multiplexing
simultaneously for seperate
channels of the specified input
module
5
-
17
$AA6
Read Channel
Status
Ask the specified input module to
return the status of all eight
channels
5
-
18
$AA0
Span Calibration
Calibrate the analog input module
to correct for gain errors
5
-
19
$AA1
Offset Calibration
Calibrate the analog input module
to correct for offset errors
5
-
20
$AA3
CJC Status
Returns the value of the CJC
sensor for a specified analog input
module
5
-
25
$AA9
SNNNN
CJC Offset
Calibration
Calibrates the CJC sensor for
offset errors
5
-