User Manual
Chapter 4
Chapter 4 Command Set
4-15
ADAM-4017+ Command Table
Command
Syntax
Command Name
Command Description
Page
No.
%AANNTTCCFF
Configuration
Set the address, input range, baud rate,
data format, checksum status and/or
integration time for the specified analog
input module
5
-
4
$AA2
Configuration
Status
Return the configuration parameters for
the specified analog input module
5
-
10
$AAF
Read Version
Return the firmware version code from the
specified analog input module
5
-
12
$AAM
Read the Module
Name
Return the modu
le name from the
specified analog input module
5
-
13
#AA
Read Analog Input
from all Channels
Return the input values from all channels
of the specified analog input module
5
-
14
#AAN
Read Analog Input
from Channel N
Return the input value from channels
number N of the specified analog input
module
5
-
16
$AA5VV
Enable/disable
Channels for
Multiplexing
Enables/disables multiplexing
simultaneously for seperate channels of
the specified input module
5
-
17
$AA6
Read Channel
Status
Ask the specified input modu
le to return
the status of all eight channels
5
-
18
$AA0
Ci
Span Calibration
Gain error calibrate of assignment channel,
User have to input the external standard source
for calibrating process
5
-
27
$AA1
Ci
Offset Calibration
Offset error calibrate of assign
ment channel,
User have to input the external standard source
for calibrating process
5
-
28
$AA7CiRrr
Input
R
ange
Setting
Input range setting individually
5
-
29
$AA8Ci
Read I
nput
Range
Get the input
range
of the assignment
channel
5
-
30
$AAXnnnn
Watchdog
Timer
Setting
Set communication
WDT
cycle
time from
0000 ~ 9999 (unit: 0.1 second. if value is
0000, the communication WDT function
will be disable)
5
-
31
$AAY
Read Watchdog
Timer Setting
Read the
cycle time
setting of
communication WDT
5-32