User Manual

Command Set
4-
12
ADAM 4000 Series User’s Manual
ADAM-4016 Command Table
Command Syntax
Command Name
Command De
scription
Page No.
%AANNTTCCFF
Configuration
Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analog input module
5
-
4
$AA2
Configuration Status
Return the configuration
parameters for the specified
analog input module
5
-
10
$AAF
Read Firmware
Version
Return the firmware version code
from the specified analog input
module
5
-
12
$AAM
Read Module Name
Return the module name from the
specified analog input module
5
-
13
#AA
Read Analog Input
Return
the input value from the
specified analog input module in
the currently configured data
format
5
-
14
$AA0
Span Calibration
Calibrate an analog input module
to correct for gain errors
5
-
19
$AA1
Offset Calibration
Calibrate an analog input module
to correct for offset errors
5
-
20
#**
Synchronized
Sampling
Orders all analog input modules to
sample their input values and store
them in special registers
5
-
21
$AA4
Read Synchronized
Data
Returns the value that was stored
in the specified module's register
after the #** command
5
-
22
$AA6
Get Excitation
Voltage Output Value
Returns either last value sent to
specified module by $AA7
command, or start-up output
voltage
5
-
65
$AA7
Excitation Voltage
Output
Direct output excitation voltage
data to a specified module
5
-
66
$AAS
Start
-
up Voltage
Output Configuration
Stores a default value in a
specified module. The output value
will take effect upon atartup.
5
-
67
$AAE
Trim Calibration
Trims specified module a number
of units up or down
5
-
69
$AAA
Zero Calibration
Tell
s the module to store
paramenters for zero calibration
5
-
70
$AAB
Span Calibration
Tells the module to store
parameters for span calibration
5
-
71