User Manual
Command Set
4-
10
ADAM 4000 Series User’s Manual
ADAM-4013 Command Table
Command Syntax
Comm
and Name
Command Description
Page No.
%AANNTTCCFF
Configuration
Sets the address, baud rate, data
format, checksum status, and/or
integration time for a specified
analog input module
5
-
4
#AA
Analog Data In
Returns the input value from a
specified analog input module in
the currently configured data
format
5
-
14
$AA0
Span Calibration
Calibrates an analog input moudle
to correct for gain errors
5
-
19
$AA1
Offset Calibration
Calibrates an analog input moudle
to correct for offset errors
5
-
20
#**
Synchronize
d
Sampling
Orders all analog input modules to
sample their input values and store
them in special registers
5
-
21
$AA4
Read Synchronized
Data
Returns the value that was stored
in the specified module's register
after the #** command
5
-
22
$AA2
Configuratio
n Status
Returns the configuration
parameters for the specified
analog input module
5
-
10
$AAF
Read Firware
Version
Returns the firmware version code
from the specified analog input
module
5
-
12
$AAM
Read Module Name
Returns the module name from the
specified analog input module
5
-
13