A.2.4 ADAM-2031Z
Wireless Sensor Network Temperature and Humidity Sensors Node
03 Read Holding Registers
Table A.5: ADAM-2031Z Mapping Table
Address 4X Description Attribute Value
40001 Temperature Input Read 0x0000 ~ 0xFFFF*
40002 Humidity Input Read 0x0000 ~ 0xFFFF**
40211 Module Name 1 Read 0x2031
40212 Module Name 2 Read 0x5A00 (ASCII Code of 'Z')
40213
Wireless Module
Firmware Version 1
Read
Version Number
(ex: 0xA210 means version A2.10)
40214
Wireless Module
Firmware Version 2
Read
Build Version Number
(ex: 0x0003 means version B03)
40301 Module Status Read
Bit 0: 0; Initial Mode
Bit 0: 1; Normal Mode
Bit 1: 0; No External Power Input
Bit 1: 1; External Power Input
40302 LQI Read
0x0000~0x00FF;
0x0000: No Signal
0x00FF: Excellent
40303 Battery Level Read
0x0000; Low
0x4000; Poor
0x8000; Normal
0xC000; Good
0xFFFF; Excellent
40304
Device Inactive Period
(Upper word)
Read
0 ~ 259200 seconds;
Maximum 3 days record
(Total 51840 steps; 5 seconds per step)
40305
Device Inactive Period
(Lower word)
40306 Link Status Read
Bit 0: Connected
Bit 1: Link Failure
Bit 2: Disconnected
Bit 3: Connecting
40307
Data Cycle Time
(Upper)
Read
0x00000001~0x00015180
(1 ~ 864000 seconds)
40308
Data Cycle Time
(Lower)
40309 LQI Percentage Read 0x0000~0x0064 (0~100%)
40310 Device Short Address Read 0x0000~0xFFFF
40311 Parent Address Read 0x0000~0xFFFF
Note!
* The temperature T is calculated by inserting temperature signal output
S
T
into the following formula (result is in
o
C).
T 46.85
175.72x
S
T
2
16
-------
+=