Advanced RF Technologies, Inc. Proprietary Document Page 27 of 43
- If you click the Factory Setting buttons for CDMA and iDEN respectively,
the following message boxes will appear:
Factory setting will erase the saved settings by the user and change all the
parameters to the factory default settings.
When you click the CDMA Factory Setting;
When you click the iDEN Factory Setting;
3.3.4 Heartbeat Time
- Heartbeat on and off (Default mode is On)
- Heartbeat periodic time
(Range: 1 to 59 min @ 1 min step, default period is 20 min)
3.3.5 Alarm Setting
CDMA
- RSSI Alarm at Donor (-100 ~ -50 dBm @ 0.5 dB step,
default value is -85 dBm)
- RF Power Alarm (2 ~ 10 dB @ 0.5 dB step, default value is 6 dB)
iDEN
- RSSI Alarm at Donor (-95 ~ -50 dBm @ 0.5 dB step,
default value is -75 dBm)
- RF Power Alarm (2 ~ 10 dB @ 0.5 dB step, default value is 6 dB)