User Manual

Epoch-S02-8002W RF Repeater
User Manual V1.0
Advanced RF Technologies, Inc. Proprietary Document Page 26 of 33
The example below distinguishes the difference between an over power soft
failure and an over power hard failure:
The threshold value for the downlink over power parameter is set to 35.0 dBm
(factory set value), a Hard Fail alarm would occur if the downlink over power
value was greater than 35.0 dBm (33 dBm is the maximum composite power
allowable). Similarly, a Soft Fail alarm would occur if the downlink over power
value was greater than 34.0 dBm but less than 35.0 dBm. Vice versa, the same
example is also applicable in the uplink side.
2.4 Default Control Settings
2.4.1 Default General Setting
Control Item Setting Value
AGC Mode ON
Downlink/Uplink HPA Mode
ON
Uplink Tracking Mode ON
Downlink/Uplink Gain 80 dB / 77 dB
Downlink/Uplink AGC Level 33 dBm
Tracking Gain Offset 3 dB
a. When
Uplink Tracking ON
mode is enabled by default, the
Tracking Gain
Offset
is set to 3 dB.
b. When
AGC ON
mode
is enabled, by default, the
Downlink/Uplink AGC
Level
is set to 33 dBm.
2.4.2 Default Alarm Setting
Setting Value
Control Item
Downlink Uplink
RSSI -95 dBm -110 dBm
Input Overload -30 dBm -30 dBm
Heartbeat On/Off ON
Heartbeat Time 20 minutes
Table 8 - Default Alarm Parameter Values of the Epoch-S02 OMS V1.XX
Table 7 - Adjustable Alarm Settings of the Epoch-S02 OMS V1.XX