Owner's manual

Page 3
The voltage rating of the device and system must always be
veried before energizing the SPD. All electrical connections
should be performed by a qualied (licensed) electrician. All
wiring must comply with the National Electrical Code (NEC)
and applicable local codes.
Maintenance of this Surge Protective Device should
be performed by qualied electrical personnel only.
During normal operation, hazardous voltages are
present inside the unit.
When servicing this unit, be sure to follow all electrical
safety precautions.
All power sources to this unit should be locked off
before servicing. This will prevent the risk of receiving
an electrical shock.
WARNING
VERIFY ALL POWER CIRCUITS ARE DE-ENERGIZED
BEFORE MAKING CONNECTIONS
!
S50A is a Type 1 SPD. S50A is suitable for use almost
anywhere (not as a plug-in SPD). Type 1 SPDs are
evaluated more rigorously by UL 1449 for 2008 NEC®
Article 285 compliance. Type 1 SPDs and their connecting
leads have been evaluated for line side applications
without need for supplemental overcurrent protection.
Type 1 SPDs include internal overcurrent protection. As a
generalization, there are practical maintenance reasons for
installing on the load side of the main overcurrent device
(i.e. Type 2 installation). When connected on load side of
main disconnect, we recommend connecting via a 30A
circuit breaker due to 10 AWG conductors. The circuit
breaker serves as a disconnect switch and provides NEC®
imposed short circuit protection to the conductors in Type
2 or 4 applications. (cUL units are Type 2 due to different
cUL criteria.)
Installation
Pre-Plan your installation. You need to accomplish the
following:
Meet all National and Local codes (NEC
®
Article
285 and UL 1449 address SPDs)
Conrm System voltage to SPD voltage (120V
SPD will fail instantly on 240V, 277V, etc.)
Mount SPD as close to panel or equipment as
possible to keep leads short (long leads hurt
performance substantially)
Ensure leads are as short and straight as
possible, including neutral. If using a breaker,
use a breaker position that is close to the SPD
and the panel’s neutral
If using a breaker, recommended breaker size is
30A due to 10 AWG conductor
Make sure system is grounded per NEC
®
and
clear of faults before energizing SPD (inadvertent
system problem may fail SPD).
Never Hi-Pot test Any SPD (will prematurely fail
SPD)
1. Use voltmeter to check voltages and ensure correct
SPD. See Data Sheet for specs & wire-outs
2. Determine Mounting method (See Figure 2) –
weather resistant equipment may be required
3. Remove power from panel/source. Conrm panel/
source is deenergized.
4. Identify breaker location and SPD location. Position
SPD such that LED is best visible.
5. Mount SPD – weather resistant applications require
additional sealing, o-rings, etc. (not included)
- Remove an appropriately sized knockout from
panel.
- Connect conductors as appropriate – short and
straight as possible
6. Label or mark conductors as appropriate (neutral:
white, energized: black)
7. Make sure system is bonded per NEC
®
and is clear
of hazards or faults before energizing (N-G bonding
not per NEC
®
will fail SPDs: #1 cause of SPD
failures)
8. Energize and conrm proper operation of green LED
indicator and/or options.
A
B
GN
BREAKER
Typical Panel Installation
(Type 1 or individual equipment installations may vary)
Use closest breaker to
SPD
Locate SPD close to
intended breaker
Keep Leads Short as
Possible
Avoid Sharp Bends
Outdoor installation requires
appropriate weather sealing
at nipple (gasket, sealing
conduit, etc.)
To Protected
Loads
Figure 1
Rotate S50A such
that LED indicator is
most visible
Sealing gasket: two choices
1.) At 3/4" nom. thread: ID is 1.05"
2.) At 0.14" high 'base step': ID is 1.25"
Figure 2