User guide

6
INSTALLATION
Pre-Plan your installation. You will need to accomplish the following:
Meet all National and Local codes. (NEC
®
Article 285 addresses SPDs)
Mount SPD as close to panel or equipment as possible to keep leads short.
Ensure leads are as short and straight as possible, including neutral and ground.
Consider a breaker position that is closest to the SPD and the panel’s neutral & ground.
Suggested breaker & conductor size is 60A-30A with 6 AWG.
Make sure system is grounded per NEC
®
and clear of faults before energizing SPD.
The following options or implementations require extra consideration. See appropriate sections
within this manual:
Internal or Integral Mount Installation inside electrical gear (page 5)
Flush Mount Option (page 6)
Retro-t where no breaker positions are available (page 6)
UL/NEMA 3R Drain Holes (page 6)
1. Use a voltmeter to check all voltages to ensure correct SPD.
2. If SPD has Dry Contact, Remote Monitoring or Remote Display, pre-plan their installation.
3. Remove power for panel. Conrm panel is deenergized.
4. Identify connection/breaker location and SPD location.
5. Make sure leads are short! Reducing inches matter! Pretend that connector leads cost you
$1000/foot to make leads short!
6. Remove an appropriately sized knockout from panel. Create an appropriately sized hole in the
SPD enclosure.
7. Mount SPD.
8. Connect conductors as appropriate – short and straight as possible
(Note that Hi-Legs are Phase B).
9. Label or mark conductors as appropriate (neutral: white, ground: green, energized:
black, hi-leg: orange).
10. Make sure system is bonded per NEC
®
and is clear of hazards or faults before energizing.
(N-G bonding not per NEC
®
will fail SPDs: #1 cause of SPD failures.)
11. Energize and conrm proper operation of indicators and/or options.
Figure 7
TYPICAL PANEL INSTALLATION
A
BC
GN
BREAKER
Phase C
Service
Phase B
Phase A
Surge Counter
Advanced Protection Technologies
Silence
Test CountReset
Use closest breaker to SPD
Locate SPD close to intended breaker
Keep Leads Short as Possible
Avoid Sharp Bends
Outdoor installation requires appropriate
weather sealing at nipple (o-ring, sealing
conduit, etc.)
To Protected Loads