Operation Manual
61180019L1-5A Issue 1, May 2004 13
NOTE
The CO X.25 network administrator must
configure the X.25 switch for the Total Access
1500 19-Inch Chassis, accomplishing tasks
such as assignment of an LDN number for the
chassis.
Connect 10Base-T
The Total Access 1500 System can provide SNMP
management capability over an Ethernet. Access to the
network is via the RJ-45 10Base-T connector,
J33,
located on the upper right side of the backplane.
WARNING
The 10Base-T Ethernet interface MUST NOT
be metallically connected to interfaces which
connect to the Outside Plant (OSP) or its
wiring. This interface is designed for use in
intra-building interfaces only. The addition of
Primary Protectors is not sufficient protection
in order to connect these interfaces metallically
to OSP wiring.
To connect the Total Access 1500 19-Inch Chassis to
the Ethernet ring, simply plug the male RJ-45 modular
connector into the female RJ-45 port,
J33, on the Total
Access 1500 19-Inch Chassis backplane. When
planning the cable run to the Total Access 1500 19-Inch
Chassis, be sure to allow enough cable for routing the
cable to the right from the backplane connector to the
frame and for tie off in accordance with CO SOP.
There are two provisional items in the SCU: Telnet port
and TCP/IP port. Specify the Telnet port to access
menus over the Ethernet, and specify the TCP/IP port to
issue TL1 commands.
Connect to PairGain Test Controller (PGTC)
Use a straight through 50-pin amp cable to connect the
PairGain Test Controller to the PGTC interface (
P5) of
the Total Access 1500 19-Inch Chassis.
P5 accepts a
female connector.
3. MAINTENANCE
The Total Access 1500 19-Inch Chassis does not require
routine maintenance for normal operation.
ADTRAN does not recommend that repairs be
attempted in the field. Repair services may be obtained
by returning the defective unit to ADTRAN. Refer to
the Warranty and Customer Service section for further
information.
4. SPECIFICATIONS
Specifications for the Total Access 1500 19-Inch
Chassis are detailed in Table 2.
Table 2. Specifications
Power Requirements
Input DC Voltage: –42 VDC to –56 VDC
DC Voltage Nominal: –48 VDC
Maximum Current: (5-amp fused) on PSU
Environmental
Operating Temperature: –40°C to 65°C
Storage Temperature: –40°C to 85°C
Relative Humidity: Up to 95% noncondensing
Physical
Dimensions: 3.50 in. H × 19.00 in. W ×
10.75 in. D
Weight fully loaded: 20 lbs.
Weight empty: 10 lbs.
Part Number
Total Access 1500 19-Inch
Chassis:
1180019L1