Installation guide

NetVanta 1000/1000R Series Hardware Installation Guide Unit Installation
61200500L1-34J Copyright © 2006 ADTRAN, Inc. 45
NetVanta 1224STR (DC)
The DC-powered NetVanta 1224STR connects to a centralized DC power source via the four-position
power connector on the rear of the chassis (see Figure 9 on page 24). Power and ground connections
require copper conductors and a ring lug.
Figure 23. Grounding the NetVanta 1224STR (DC)
Instructions for Connecting DC Power Source to the NetVanta 1224STR
Step Action
1 With the power disconnected, connect the primary power source to input A of the power
connector.
2 Connect a ground wire (fitted with a loop terminal end) to the grounding point using the screw
provided. Connect the other end of the ground wire to a protective earth ground. See Figure 23
below.
3 If using a backup power source, connect it to input B of the power connector.
Power to the NetVanta 1224STR DC System must be from a reliably grounded 24 or
48 VDC.
Use only copper conductors when making power connections.
Install unit in accordance with the requirements of NEC NFPA 70.
The branch circuit overcurrent protection shall be a fuse or circuit breaker rated
minimum 48 VDC, maximum 10 A.
A readily accessible disconnect device, that is suitably approved and rated, shall be
incorporated in the field wiring.
Maximum recommended ambient operating temperature is 50
°C.
The 10/100BaseT and Gigabit-Ethernet interfaces MUST NOT be metallically connected
to interfaces which connect to the Outside Plant or its wiring. These interfaces are
designed for use as intra-building interfaces only. The addition of primary protectors is
not sufficient protection in order to connect this interface metallically to OSP wiring.
To comply with GR-1089-CORE, Issue 3, this equipment MUST only be installed in a
DC-C (common) bonding and grounding environment. It may not be utilized in a DC-I
(isolated) bonding and grounding environment.