Specifications

MX410/MX412 System Manual
2-2 61189500L1-1F
POWER REQUIREMENTS
Table 2-3 lists the current draw at –48 VDC (operating range of –42 VDC to –60 VDC) and ±24
VDC (operating range of ±22 VDC to ±27 VDC) with redundant PSUs installed (MX410 only).
Table 2-4 provides data for determining the recommended fuse for the fuse and alarm panel
that services the MX410/MX412.
Table 2-1. MX410 and MX412 Configuration Codes
Code Input Output
Power Code (PC) F C
Telecommunication Code (TC) X X
Installation Code (IC) A
Table 2-2. MX410 PSU Configuration Codes
Code Input Output
Power Code (PC) F C
Telecommunication Code (TC)
Installation Code (IC) A
Table 2-3. Current Draw at –48 VDC and ±24 VDC
Part Number Equipment Maximum Current Draw
at –48 VDC
Maximum Current Draw
at ±24 VDC
1189500L1 MX410 0.23 amps 0.41 amps
1189512L1 MX412 0.36 amps 0.76 amps
Table 2-4. Fuse Recommendations
System Voltage Recommended Fuse
–48 VDC 2 amps, slow-blow
±24 VDC 2 amps, slow-blow