Installation guide
Unit Installation NetVanta 6240/6250 Series HIG
28 Copyright © 2013 ADTRAN, Inc. 61700202G1-34B
Figure 6. Supplying DC Power and Grounding the NetVanta 6250
Instructions for Connecting DC Power Source to the NetVanta 6250
Step Action
1 Insert the positive terminal of the DC power source into left position of the two-position terminal
block (labeled RTN on the NetVanta 6250). Tighten the screw.
2 Insert the negative terminal of the DC power source into the right position of the two-position
terminal block (labeled -48V on the NetVanta 6250). Tighten the screw.
3 With the power disconnected, insert the terminal block into the receptacle labeled DC IN until it
is firmly seated against the chassis. Tighten the two screws.
4 Connect a ground wire (fitted with a number 8 ring terminal end) to the grounding lug using the
screw provided and the appropriate crimping tool (AMP P/N 59250 T-EAD Crimping Tool or
equivalent). Connect the other end of the ground wire to a protective earth ground. See
Figure 6 below.
5 Supply DC power to the unit.
• Power to the NetVanta 6250 system must be from a reliably grounded 48 VDC.
• Use only copper conductors when making power connections.
• Install unit in accordance with the requirements of NEC NFPA 70.
• The branch circuit overcurrent protection shall be a fuse or circuit breaker rated
minimum -48 VDC, maximum 10 A.
• A readily accessible disconnect device, that is suitably approved and rated, shall be
incorporated in the field wiring.
• Maximum recommended ambient operating temperature is 50
°C.
CRAFT
BBU
AC INPUT
DC IN
RTN -48V