Installation guide
Unit Installation NetVanta 6240/6250 Series HIG
24 Copyright © 2013 ADTRAN, Inc. 61700202G1-34B
Mounting Options
The unit may be installed in rackmount, wallmount, or tabletop configurations. The following sections provide
step-by-step instructions for rack mounting and wall mounting.
Rack Mounting the NetVanta
The NetVanta is a 1U-high, rack-mountable unit that can be installed into 19-inch or 23-inch equipment racks.
The following steps guide you in mounting the NetVanta into a rack.
ADTRAN recommends 1U (1.75 inches) of separation above and below the
NetVanta 6240/6250 Series unit. This spacing allows the unit to dissipate heat. The design
of the NetVanta 6240/6250 Series uses the chassis to distribute heat generated by the unit’s
internal cards. This design allows the unit to operate without a cooling fan, ensuring the
overall reliability of the unit.
• If installed in a closed or multi-unit rack assembly, the operating ambient temperature
of the rack environment may be greater than room ambient temperature. Therefore,
consideration should be given to installing the equipment in an environment compatible
with the maximum ambient temperature specified by the manufacturer.
• Installation of the equipment in a rack should be such that the amount of air flow
required for safe operation of the equipment is not compromised.
• Be careful not to compromise the stability of the equipment mounting rack when
installing this product.
• Consideration should be given to the connection of the equipment to the supply circuit
and the effect that overloading the circuit might have on overcurrent protection and
supply wiring. Appropriate consideration of equipment nameplate ratings should be
used when addressing this concern.
• Reliable grounding of rack-mounted equipment should be maintained. Particular
attention should be given to supply connections other than direct connections to the
branch circuit (e.g., use of power strips).
Instructions for Rack Mounting the NetVanta
Step Action
1 Attach universal rackmount brackets in the appropriate (either 19-inch or 23-inch) position using
the supplied screws.
2 To allow proper grounding, scrape the paint from the rack around the mounting holes where the
NetVanta will be positioned.
3 Position the NetVanta in a stationary equipment rack allowing 1U space above the unit for
ventilation.
4 Have an assistant hold the unit in position as you install two mounting bolts through the unit’s
brackets and into the equipment rack using a #2 Phillips-head screwdriver.
5 Apply power to the unit (refer to Supplying Power to the Unit on page 27 or Supplying DC Power
to the NetVanta 6250 on page 27 as appropriate).