User manual

ADT-HC4500 CNC Flame/Plasma Controller
88
Isolation voltage: 2500V DC
Counting input:
Channel: Main axis ABZ-phase coding input, all photovoltaic isolation
Maximum counting frequency: 2MHz
Input voltage: 5-24V DC
High level >1.5V
Low level <1.0V
Isolation voltage: 2500V DC
Pulse output:
Channel: 3 pulses, 3 directions, all photovoltaic isolation
Maximum pulse frequency: 2MHz
Output type: 5V differential output
Output mode: Pulse + Direction, or Pulse + Pulse
Digital output:
Output channel: 16 channels, all photovoltaic isolation
Output type: NPN open-collector output 12-24VDC, maximum current can reach 100mA
RS-232 baud rate (bps):
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
2.3 Electrical connection
2.2.1 Motor control interface——15-core socket (Male)