Specifications
Our energy working for you.™
www.cumminspower.com
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation.
D-3235g (4/08)
Alternator data
Voltage Connection
1
Temp rise
degrees C Duty
2
Single
phase
factor
3
Max
surge
kVA
4
Winding
No.
Alternator
data sheet
Feature
Code
380 Wye, 3-phase 125 S 7327 13 ADS-515 B598
380 Wye, 3-phase 105 S 7963 13 ADS-516 B599
440 Wye, 3-phase 150 S 7284 12 ADS-515 B701
440 Wye, 3-phase 105 S 8438 12 ADS-516 B665
480 Wye, 3-phase 150 S 7695 312 ADS-335 B453
480 Wye, 3-phase 125 S 7284 12 ADS-515 B276
480 Wye, 3-phase 105 S 8438 12 ADS-516 B600
480 Wye, 3-phase 80 S 9728 12 ADS-517 B601
600 Wye, 3-phase 150 S 7695 07 ADS-335 B419
600 Wye, 3-phase 125 S 7265 07 ADS-515 B602
600 Wye, 3-phase 105 S 8253 07 ADS-516 B603
600 Wye, 3-phase 80 S 9611 07 ADS-517 B604
4160 Wye, 3-phase 150 S 6307 51 ADS-518 B606
4160 Wye, 3-phase 125 S 6307 51 ADS-518 B467
4160 Wye, 3-phase 105 S 6307 51 ADS-518 B313
4160 Wye, 3-phase 80 S 7315 51 ADS-519 B605
12470 Wye, 3-phase 125 S 6038 87 ADS-521 B609
12470 Wye, 3-phase 105 S 6685 87 ADS-522 B608
13200-13800 Wye, 3-phase 125 S 6062 91 ADS-521 B611
13200-13800 Wye, 3-phase 105 S 6833 91 ADS-522 B612
13800 Wye, 3-phase 80 S 8012 91 ADS-523 B610
Notes:
1
Limited single phase capability is available from some three phase rated configurations. To obtain single phase rating, multipy the three phase
kW rating by the Single Phase Factor
3
. All single phase ratings are at unity power factor.
2
Standby (S), Prime (P) and Continuous ratings (C).
3
Factor for the Single Phase Output from Three Phase Alternator formula listed below.
4
Maximum rated starting kVA that results in a minimum of 90% of rated sustained voltage during starting.
Formulas for calculating full load currents:
Three phase output Single phase output
Cummins Power Generation
1400 73
rd
Avenue N.E.
Minneapolis, MN 55432 USA
Phone: 763 574 5000
Fax: 763 574 5298
Important: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system
except through an approved device or after building main switch is open.
Voltage
1000 x eFactorSinglePhas x kW
0.8 x 1.73 x Voltage
1000 x kW