Specifications

Our energy working for you.™
www.cumminspower.com
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation.
D-3235g (4/08)
Optional remote radiator cooling
1
Standby
rating
Prime
rating
Continuous
rating
Set coolant capacity, L (US gal) 193 (51)
Max flow rate @ max friction head, jacket water circuit, L/min
(US gal/min)
1817 (480)
Max flow rate @ max friction head, aftercooler circuit, L/min
(US gal/min)
503 (133)
Heat rejected, jacket water circuit, MJ/min (Btu/min) 45.1 (42765)
Heat rejected, aftercooler circuit, MJ/min (Btu/min) 36.4 (34525)
Heat rejected, fuel circuit, MJ/min (Btu/min) 2.1 (2000)
Total heat radiated to room, MJ/min (Btu/min) 18.8 (17887)
Maximum friction head, jacket water circuit, kPa (psi) 69 (10)
Maximum friction head, aftercooler circuit, kPa (psi) 48 (7)
Maximum static head, jacket water circuit, m (ft) 18 (60)
Maximum static head, aftercooler circuit, m (ft) 18 (60)
Maximum jacket water outlet temp, °C (°F) 104 (220)
Maximum aftercooler inlet temp @ 25 °C (77 °F) ambient, °C (°F) 49 (120)
Maximum aftercooler inlet temp, °C (°F) 71 (160)
Maximum fuel flow, L/hr (US gph) 1685 (445)
Maximum fuel return line restriction, kPa (in Hg) 30.5 (9)
Weights
2
Unit dry weight kgs (lbs)
15254 (33629)
Unit wet weight kgs (lbs)
15781 (34790)
Notes:
1
For non-standard remote installations contact your local Cummins Power Generation representative.
2
Weights represent a set with standard features. See outline drawing for weights of other configurations.
Derating factors
Standby
Engine power available up to 260 m (853 ft) at ambient temperatures up to 40 °C (104 °F). Above these
elevations, derate at 3.3% per 305 m (1000 ft) and 8.4% per 10 °C (18 °F).
Prime
Continuous
Ratings definitions
Emergency standby power
(ESP):
Limited-time running power
(LTP):
Prime power (PRP):
Base load (continuous)
power (COP):
Applicable for supplying power
to varying electrical load for the
duration of power interruption of
a reliable utility source.
Emergency Standby Power (ESP)
is in accordance with ISO 8528.
Fuel Stop power in accordance
with ISO 3046, AS 2789, DIN
6271 and BS 5514.
Applicable for supplying power to
a constant electrical load for
limited hours. Limited Time
Running Power (LTP) is in
accordance with ISO 8528.
Applicable for supplying power
to varying electrical load for
unlimited hours. Prime Power
(PRP) is in accordance with ISO
8528. Ten percent overload
capability is available in
accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Applicable for supplying power
continuously to a constant
electrical load for unlimited
hours. Continuous Power (COP)
is in accordance with ISO 8528,
ISO 3046, AS 2789, DIN 6271
and BS 5514.