Air
Standby
rating
Prime
rating
Continuous
rating
Combustion air, m
3
/min (scfm)
183 (6455)
Maximum air cleaner restriction, kPa (in H
2
O)
6.2 (25)
Alternator cooling air, m
3
/min (cfm)
161 (5700)
Exhaust
Exhaust gas flow at set rated load, m3/min (cfm)
445 (15705)
Exhaust gas temperature, °C (°F)
479 (895)
Maximum exhaust back pressure, kPa (in H2O)
6.7 (27)
Standard set-mounted radiator cooling
Ambient design, °C ( °F)
40 (104)
Fan load, kW/m
(HP)
57.4 (77)
Coolant capacity (with radiator), L (US gal)
492 (130)
Cooling system air flow, m
3
/min (scfm)
2294 (81000)
Total heat rejection, MJ/min (Btu/min)
94.1 (97177)
Maximum cooling air flow static restriction, kPa (in H
2
O)
0.12 (0.5)
Maximum fuel return line restriction kPa (in Hg)
23.7 (7)
Optional set-mounted radiator cooling
Ambient design, °C (°F)
Fan load, kW/m (HP)
Coolant capacity (with radiator), L (US gal)
Cooling system air flow, m
3
/min (scfm)
Total heat rejection, MJ/min (Btu/min)
Maximum cooling air flow static restriction, kPa (in H
2
O)
Maximum fuel return line restriction, kPa (in Hg)
Optional heat exchanger cooling
Set coolant capacity, L (US gal)
Heat rejected, jacket water circuit, MJ/min (Btu/min)
Heat rejected, aftercooler circuit, MJ/min (Btu/min)
Heat rejected, fuel circuit, MJ/min (Btu/min)
Total heat radiated to room, MJ/min (Btu/min)
Maximum raw water pressure, jacket water circuit, kPa (psi)
Maximum raw water pressure, aftercooler circuit, kPa (psi)
Maximum raw water pressure, fuel circuit, kPa (psi)
Maximum raw water flow, jacket water circuit, L/min (US gal/min)
Maximum raw water flow, aftercooler circuit, L/min (US gal/min)
Maximum raw water flow, fuel circuit, L/min (US gal/min)
Minimum raw water flow @ 27 °C (80 °F) Inlet temp, jacket water
circuit, L/min (US gal/min)
Minimum raw water flow @ 27 °C (80 °F) Inlet temp, aftercooler circuit,
L/min (US gal/min)
Minimum raw water flow @ 27 °C (80 °F) Inlet temp, fuel circuit, L/min
(US gal/min)
Raw water delta P @ min flow, jacket water circuit, kPa (psi)
Raw water delta P @ min flow, aftercooler circuit, kPa (psi)
Raw water delta P @ min flow, fuel circuit, kPa (psi)
Maximum jacket water outlet temp, °C (°F)
Maximum aftercooler inlet temp, °C (°F)
Maximum aftercooler inlet temp @ 25 °C (77 °F) ambient,
°C ( °F)
Maximum fuel return line restriction, kPa (in Hg)