Control system
Operator panel features
Analog AC metering panel - Provides color-coded
display of generator set output voltage, current,
frequency, power factor and kW. All phases of voltage
and current are simultaneously displayed. Easy to see
output status from a distance.
Graphical data display - Allows operator to view all
engine and alternator data; perform operator adjustments
for speed, voltage and time delays; view fault history; and
set up and adjust the generator set (set up requires
password access). A portion of the display is allocated
to display system status including alarm and shutdown
conditions. Display is controlled by sealed membrane
switches. Up to 9 lines of data can be displayed with
approximately 26 characters per line.
LED status lamps - The status lamps indicate remote
start command (green), not in auto (red-flashing), warning
(amber) and shutdown (red).
Mode selector switch - Off/manual/auto and run/stop
switches allow remote automatic starting or manual
starting from the operator panel. Panel includes an LED
lamp to indicate manual mode operation.
Exerciser switch - Automated exercise function in the
control allows an operator to initiate an exercise period
and have it automatically completed by the control.
Fault reset switch - Allows the operator to reset the
control after a warning or shutdown condition. LED lamp
with switch indicates that a fault is present on the
system.
Panel lamps and switch - Operator panel can be
illuminated by a series of high-intensity LED lamps
controlled by a membrane switch on the panel. Panel
lamps include a time delay to automatically switch off
after a preset time period.
Emergency stop switch - Provides positive and
immediate shutdown of the generator set on operation.
Construction - Operator panel is a sealed design with
membrane switches for most functions. Mechanical
switches are oil-tight design. Plug interfaces are
provided to the generator set control system. Display
panel labeling is configurable for language.
Standard control functions
• Integrated Isochronous governing and fuel control
system.
• Integrated 3-phase sensing voltage regulation system
with automatic single and three phase fault regulation.
• Integrated AC protective functions include over/under
voltage, short-circuit, overcurrent (warning and
shutdown) and overload.
• Integrated engine management system including
configurable cycle-cranking functions and configurable
start sequence.
• Comprehensive warning and shutdown protection
including customer configurable warning and shutdown
conditions.
• Comprehensive data displays including 3-phase AC
voltage, current, power factor, kW and kVA; engine oil
pressure, coolant temperature, DC volts and other
service functions; operating history (load and fault
conditions) and system setup information.
Options
Integrated digital paralleling controls including options
for semi-automatic and automatic (isolated bus)
applications.
LonMark compliant network interface.
Control anti-condensation heater.
Key-type mode select switch.
Relay outputs for genset running, common warning
and common shutdown.
Exhaust temperature alarm.
Alternator temperature alarm(s).
Centinel™ lube oil burn system.
Power transfer control function to allow generator set
to control remote power circuit breakers for open, fast
closed or soft (ramping) power transfer from a utility
source to the genset (2 minute maximum fail-to-
disconnect timer).