Specifications
Easy field set up
H
W
D
10 7.66" (195mm) 6.48" (165mm) 10.50" (267mm)
Amps Width Depth Height
Housing Dimensions Table
Mechanical
Housing: Wall mount
Material: .125" thick, non-corroding brushed
aluminum
Connections: Hard-wired input, output and alarm
terminations
Cooling: Natural convection
Environmental
Operating -20C to +60C. Full output available
temperature: to +40C. Overtemperature
protection provided.
Humidity: 5% to 95%, non-condensing.
Circuit card is conformally coated.
Altitude: 0-2000 meters with no derating.
Automatic derating above 2000
meters.
Vibration: 2G sinusoidal from 10 Hz to 150 Hz
per UL 991.
Controls & Adjustments
Battery setting: 6 discrete programs for flooded,
VRLA and Ni-Cd batteries.
12/24-volt Optional 12/24-volt unit offers field
program: selection of 12 or 24 volts. Alarms
and battery programs automatically
change with output selection.
Fast-charge Fast charge can be enabled or
control: disabled in the field.
Temp comp. Local or remote temperature
control: compensation can be enabled or
disabled in the field.
Standards Compliance
Safety: UL 1236, UL 1012
CSA 22.2 No. 107.2-M89
EN 60335-2-29
NFPA 110
Vibration: UL 991, Class B
EMC: FCC Part 15, Class B
ICES-003
EN 55011, Class A
Line harmonics: EN 61000-3-2
Immunity: EN 61000-6-2
Surge transient: ANSI/IEEE C62.41, Cat. B
EN 61000-4-5
ESD: EN 61000-4-2
Radiated immunity: EN 61000-4-3
Fast transient: EN 61000-4-4
Injected RF: EN 61000-4-6
Agency Markings
UL, CSA: C-UL listed
EN: CE marked, DOC to EN 60335
(50/60 Hz model only)