Instruction Manual
ADS XiLog+ System User Manual 
49 
Ignore Daylight Savings 
Selecting this checkbox prevents the clock in the XiLog+ from compensating 
for daylight savings time. 
Host and Alarm Numbers 
When performing remote data reporting via SMS, the XiLog+ transmits the 
data to all the host numbers designated in the Contact Details section. A host 
number corresponds to a GSM modem connected to a computer. The 
Primayer Data Manager utility running within Windows serves as the 
conduit through which the data is transferred from the GSM modem to the 
PrimeWorks software for viewing. Up to three host numbers may be entered 
in PrimeWorks, allowing data delivery to up to three different offices or 
locations. 
Up to two additional alarm numbers also may be entered.  Any SMS alarms 
generated by the logger will be sent to these numbers. The logger sends data 
only to the host number(s); however, it sends alarms to both the host and 
alarm numbers, when necessary. 
Note: To use the Primayer XMS system for remote data delivery over 
the Internet, select the Use XMS Host checkbox and then select the 
appropriate network from the corresponding drop-down list. Choosing 
this option does not require entering any additional numbers or contact 
information. All distribution of data occurs within the XMS system. 
FTP Server Address 
This field displays the address of the FTP server to which the logger should 
transmit the data.  When using the Primayer XMS delivery system, enter 
www.waterlogger.co.uk. When using another FTP server, enter the address 
without an FTP prefix. 
FTP Username 
This field displays the username for logging onto the FTP server. Enter the 
appropriate username for the user. 
Note: When using the Primayer XMS system, defer to ADS Client 
Services to obtain the proper login details. 