Instruction Manual
ADS XiLog+ System User Manual 
44 
Threshold Alarms 
Threshold alarms generally involve designating a high and/or low threshold 
beyond or below which the XiLog+ will generate an alarm. This section 
includes descriptions for the parameters that are common only to threshold 
alarms. 
 Low Threshold 
This field represents the threshold below which the logger will trigger a low 
alarm. Enter the threshold manually or use the up/down arrows. 
 High Threshold 
This field represents the threshold above which the logger will trigger a high 
alarm. Enter the threshold manually or use the up/down arrows. 
Profile and Envelope Alarms 
Profile and Envelope alarms are more complex alarms that involve 
designating a different threshold value for the high and low alarms for every 
15-minute increment throughout the day. For example, the high thresholds 
designated for generating flow alarms may be much lower through the night 
than during the day. 
Selecting either option displays a graph for creating and editing the profile or 
envelope. 
Importing sample data from the database 
The simplest way to establish a profile or envelope alarm is to import 
historical data from the site in the following way: 
1.  Select the appropriate logging function from the Available Data list. 
2.  Select the radio button corresponding to the option for the number of 
days for which to import data. 
 Single day Choose this option to import data for only one day, 
and then designate the date for which to import the data using the 
Start Date calendar control. 