Instruction Manual
ADS XiLog+ System User Manual 
39 
Several options also are included in the Sensor Types drop-down list for 
performing event logging using digital sensors. To implement event logging, 
select one of the corresponding options from the list. 
Pulse Direction 
This drop-down list contains the options for specifying how a bidirectional 
sensor indicates reverse flow. 
Logging Interval 
This drop-down list includes the options for designating the measurement 
interval at which to log data on this channel. The options available range 
from 5 seconds to 24 hours. The data logged on the channel represents 
averaged data (based on the number of samples taken). XiLog+ records the 
averaged data and daily minimum and maximum values for the channel. The 
digital channel also records daily volume. Transmitting the meter reading 
from the site to the logger, as below, will ensure remote tracking of the site 
meter reading is accurate. 
Units 
This drop-down list contains the options for selecting the units of measure in 
which to log the data. 
Continuous Power 
Selecting this checkbox ensures the channel provides uninterrupted power to a 
pulse (sensor) unit that requires continuous power. Use this option only when 
the required by the sensor type. 
Combine Flows 
Selecting this checkbox adds together the flow totals from a combination 
meter, which represents two meters (larger and smaller) working in parallel, 
before the data is transmitted to the logger to provide one flow rate and meter 
reading. In this scenario, flows exceeding a certain rate will flow through the 
larger meter and flows occurring below a certain rate will flow through the 
smaller meter. The outputs from both meters connect to the logger on two 
different pulse trains of a single channel. 