Setting up Alarms
Decide how many alarms will be used. Each alarm has a
programmable name, a trigger source, a text message, 3 telephone
numbers, and the ability to activate or deactivate a control.
E-mail option adds 2 e-mail addresses to the alarm configuration.
Voice option adds 3 voice telephone numbers to the configuration.
For example, set up Alarm 1 as follows (assuming e-mail and voice
options are installed):
Alarm Name: Pump 1 fail
Trigger Source: Pump status 1
Trigger Level: “ON” (i.e., trigger when
source is “ON” or active)
Control Action: Control 1 ON - continuous
SMS / E-mail / Voice Text: Pump 1 has failed