Owner manual

C-1
A P P E N D I X C
Modbus Output
Registry Entities and Values
This appendix contains FlowShark
®
Modbus output registry entities
and values.
Description
Profile Entity
®
Units of
Measure
Registers
Flow FLOW1 MGD 40001-40002
Peak Velocity RAWVEL FPS 40003-40004
UniDepth UNIDEPTH Inches 40005-40006
Ultrasonic Depth UDEPTH Inches 40007-40008
Unadjusted Pressure
Depth
N/A Inches 40009-40010
Ultrasonic Range 0 U2 Inches 40011-40012
Ultrasonic Range 1 U3 Inches 40013-40014
Ultrasonic Range 2 U4 Inches 40015-40016
Ultrasonic Range 3 U5 Inches 40017-40018
Rain Intensity RAINI Inches/Unit
Time
40019-40020
Ultrasonic Range
(Arbitrated)
Diagnostic Inches 40021-40022
Ultrasonic
Temperature
Diagnostic Degrees F 40023-40024
Monitor Voltage BTYVOLT Volts 40025-40026
QThreshold QTHRESHOLD MGD 40027-40028