Owner manual

Modbus 9-5
Defining the Modbus Register Values
Use the information provided in the following table to select the
FlowShark output values to be received by the control system. This
table contains the most commonly configured value names and
associated register addresses.
Holding Register Definitions
Description
Profile
®
Entity
Units of Measure Registers
Flow FLOW1
(QCONTINUITY)
MGD 40001-40002
UniDepth UNIDEPTH Inches 40005-40006
Ultrasonic Depth UDEPTH Inches 40007-40008
Pressure Depth PDEPTH Inches 40053-40054
Peak Velocity RAWVEL FPS 40003-40004
Average Velocity N/A (VELOCITY) FPS 40061-40062
Rain Intensity RAINI Inches/Unit Time 40019-40020
Rain RAIN Inches 40031-40032
Number of
Samples
SAMPLES N/A 40077-40078
Analog Input 1 Varies Varies 40087-40088
Analog Input 2 Varies Varies 40089-40090
Analog Output 1 Varies Varies 40091-40092
Analog Output 2 Varies Varies 40093-40094
Monitor Battery BTYVOLT Volts 40025-40026
Radio Battery BTY_RADIO Volts 40029-40030
Additional entities and values are available. Refer to Appendix C,
Modbus Output Registry Entities and Values, for a complete list.