intrinsically safe only whe n the Ru-33 is installed outside
the manhole.
Configur ing the Monitor t o S upport the Ru-33
Configur ing the TRITON+ to support the Telog Ru-33 requires
setting three paramete rs in Qstart when establishing a new location.
Refer to Create and Configure the Monitor Location in Chapter 6,
Configuration and Activation, for more information.
Scan frequency This represents the interval at which the
monitor takes readings. These readings are available for
retrieval dir e c tly from the monitor, b ut ar e overwritten with
new data at each new interval. Therefore, ADS recommends
using the same interva l for both the scan r ate in the monitor and
the rate at which the Telog unit requests the data from the
monitor.
Modbus ID This represents the Modbus slave ID that will be
used by the Ru-33 to indicate the specific monitor from which
to request the data. ADS recommends using 55 to identify the
TRITON+.
Modbus Delay Response Thi s repr esents the amount of
time, in milliseconds, following the r e quest before the monitor
will retur n the requested Modbus output data to the Ru-33.
ADS recommends maintaini ng the 10 ms default setting.
Connecti ng t he Monitor to the Ru-33
Connecting the TRITON+ to the Ru-33 requires the ADS Triton-
Telog Comm Cable (ADS p/n 8000-0054-01). First, c onnect the
black, metal connector (with gray, plastic boot) from the comm
cable to the COMM + EXT PWR port on top of the TRITON+.