Problem
Event st atus received at customer input device from XIO
digital output is not accurate.
Possible
Causes
XIO Device may not have been properly conf i gured in
Qstart for the digi tal output.
Possible
Solutions
Verify that the HIGH_LEVEL (or HIGH_HIGH) entity has
been selected for the appropriate digi tal output from the
XIO Device in Qstart. Verify that High Threshold and
High-High Threshold have been select ed for the Depth
Alarms from the MLI Devi ce in Qstart. If changes are
required, react i vat e the monit or.
Contact your regional ADS representati ve.
Problem
Modbus com municat i on i s not successful .
Possible
Causes
Wiring to RS-485 or RS-232 port on ExPAC may be
incorrect.
Communication port settings in c ustomer devic e may be
incorrect.
Modbus ID designated in Qstart may be incorrect.
ExPAC may be def ective.
Possible
Solutions
Verify wiring for RS-485 or RS-232 is correct.
Verify that the proper communication port settings have
been set in the cust omer device. Port sett i ngs should
be 19200 baud, 8 data bit s , no parity, 1 stop bit (8-N-1),
and no flow control.
Verify that the Modbus ID is correct Qstart. If the ID
requires m odi fication, update the ID and reactivate the
monitor.
Contact your regional ADS representati ve.