User Manual

Maintenance a n d Troubleshooting 10-59
Problem
Data or readings recei ved at the monit or t hrough the 4-
20 mA i nput in the XIO from the cust omer output devic e
are not accurate or were unexpected.
Possible
Causes
Wiring from XIO analog input to external 4-20 m A output
device m ay not be properl y c onnected.
XIO Device may not have been properly confi gured
through Qstart.
Analog m odul e i n XIO may not have been setup
properly or may be defective.
Possible
Solutions
Verify wiring between the XIO input and t he external
output devic e has been properly connected.
Verify that the correct anal og i nput entity has been
selected, the sc al e has been set properly, and t he
appropriate data c heckboxes have been select ed i n
Qstart. If necessary, adjust the conf i gurat i on and
reactivat e t he monitor.
Contact your regional ADS representati ve.
Problem
Data rec ei ved at t he monitor t hrough t he di gi tal input in
the XIO from the customer output devic e is not
consistent with output .
Possible
Causes
XIO Device may not have been properly c onfigured in
Qstart for the digi tal input.
Possible
Solutions
Verify that the D1 (or D2) entity and the S to re Data
check box have been selected for the appropriate digital
input from the XIO Device configuration in Qstart. If
changes are required, reactivate the monitor. (Note:
The D1 corresponds to digital output 1 and D2
corresponds to digital output 2.)
Contact your regional ADS representati ve.