Maintenance a n d Troubleshooting   10-59 
Problem 
Data or readings recei ved at the monit or t hrough the 4-
20 mA i nput in the XIO from the cust omer output devic e 
are not accurate or were unexpected. 
Possible 
Causes 
Wiring from XIO analog input to external 4-20 m A output 
device m ay not be properl y c onnected. 
XIO Device may not have been properly confi gured 
through Qstart. 
Analog m odul e i n XIO may not have been setup 
properly or may be defective. 
Possible 
Solutions 
Verify wiring between the XIO input and t he external 
output devic e has been properly connected. 
Verify that the correct anal og i nput entity has been 
selected, the sc al e has been set properly, and t he 
appropriate data c heckboxes have been select ed i n 
Qstart. If necessary, adjust the conf i gurat i on and 
reactivat e t he monitor. 
Contact your regional ADS representati ve. 
Problem 
Data rec ei ved at t he monitor t hrough t he di gi tal input in 
the XIO from the customer output devic e is not 
consistent with output . 
Possible 
Causes 
XIO Device may not have been properly c onfigured in 
Qstart for the digi tal input.  
Possible 
Solutions 
Verify that the D1 (or D2) entity and the S to re Data  
check box have been selected for the appropriate digital 
input from the XIO Device configuration in Qstart. If 
changes are required, reactivate the monitor.  (Note: 
The D1 corresponds to digital output 1 and D2 
corresponds to digital output 2.) 
Contact your regional ADS representati ve. 