Edit the following parameters corresponding to the downward-
looking ultra s onic (s mart) depth sensor as necessary:
Note: Edit the parameters for an Ultrasonic Depth Sensor
equipped with the pressure option through the S urface
Combo Sensor device. Refer to Editing the Surface
Combo Sensor Device on page 6-28 for more information.
Parameters
Note: Under normal conditions, the pa r a meters in this
section (Parameters) should not require modification.
However, if additional adjustments are necessary, refer to
the detailed description of each parameter.
Electronic Offset Enter the difference that exists between
the smart depth sensor readings and the manually measured
depth, when applicable. The default value is 0.
Note: An electronic offset is rarely needed. An offset
greater than +/- 0.5 inches (13 mm) typically indicates that
the physical offset or pipe height has been measured or
recorded incorrectly.
Mode Select the mode in which yo u want the smart depth
sensor to operate based on environmental factors or site
constraints. ADS recommends using the Normal setting for
pipe heights ranging from 6 to 24 inches (15 to 61 cm) and
High for pip e heights gr eater than 24 i nches (61 cm) under
most conditions. However, if erratic Smart Depth readings
occ ur, co ns ider changing the Power setting.