User Manual
Configura tion and Activation   6-39 
most common option for selection. ADS recommends 
using this setting for most monitoring applications. 
  Backward Choose this option for monitoring points at 
which the Surface Co mbo Sensor has been positioned 
facing d ownstream and to ensure the monitor only analyzes 
flows moving away from the face of the sensor. One 
application in which this would be the preferable option 
would be for measuring velocity in an outgoing line 
following two incoming lines in the manhole. 
  Backward Bidirectional Choose thi s option when the 
Surface Combo Sensor is installed facing d o wnstream and 
to ens ure the monit or ana lyzes flows moving bo th away 
from and toward the face of the sensor. This option would 
be beneficial, for example, when using a weir to measure 
overflows with the pote ntial of river intrusion. 
  Maximum Velocity Select the maximum expected velocity 
that will occur at the site for the monitor to use in fine-tuning 
the velocity data. The Auto (default) option serves to optimize 
the range and r esolution of the velocity data samples to match 
the characteristics of the flow. However, if the velocity 
readings at the location measure at least 10 feet per second 
(fps) on a regular basis, ADS r eco mmends choosing the 15 fps 
option for this par a meter.  
  Transmit Fr equency Select the frequency at which to 
transmit the signal. ADS recommends leaving the d efault 
setting (Normal) for most applications. However, if hydraulic 
conditions at the site are r e sulting in questionable o r e rroneous 
rea dings, conside r applying the other frequency opt ion. 
Contact ADS for assistance when necessary. 
  Gain T his value represents the factor applied to raw velocity 
(RAWVEL entity in Qstart) to determine average velocity and 
to calculate q uantity for the Flow 1(2) device. 
Note: The Cro ss Check Gain parameter do es not apply 
to the (Surcharge) Peak Velocity Sensor; therefore, it is not 
available on the Peak Velocity tab. 