User's Manual
Advanced RF Technologies, Inc.
28
3.1.2.1 LEDs
RFU has LEDs on the front panel as shown in Figure 3-10.
HARD FAIL
DL SIG LOW
SOFT FAIL
POWER
Figure 3-10 RFU LED
Table 3-2 RFU LED Specifications
ADX DAS-Module Specifications
Power
Solid Green
Module power is ON.
OFF
Module power is OFF.
Soft Fail
Solid Yellow
Soft Fail alarm exists in the RFU.
Solid Green
No Soft Fail alarms are present in the RFU.
Hard Fail
Solid Red
Hard Fail alarm exists in the RFU.
Solid Green
No Hard Fail alarms are present in the RFU.
DL SIG LOW
Solid Yellow
When DL input signal level is lower than the defined threshold
level. (default threshold value: -5dBm)
Solid Green
When DL input signal level is upper than the defined threshold
level.
3.1.2.2 RF Ports
3.1.2.2.1 DL IN/UL OUT & DPX ports
DL IN/UL OUT & DPX Ports (refer to Figure 3-7) are located at the back of RFU and can be connected directly to
the BTS. The RFU can support incoming signal strength from 0 to 25dBm(in case of BT and VU, -15~37dBm).
BT RFU does not have DL IN port because of TDD(Time division duplex) system.
VU RFU does not have DPX port because there is externally optional Duplexer customized by user requirement
for VHF/UHF system.
3.1.2.2.2 DL OUT/UL IN
DL OUT/UL IN Ports (refer to Figure 3-7) are located at the front of the RFU and connect directly to the HE
Channel Combiner (ADX-H-CHC).
3.1.2.3 Communication Port
The ADX-H-NMS monitors and controls the RFU via this port. DC Power is also provided to the RFU via this port.
Figure 3-11 Communication Port (RFU)
3.1.3 Channel Combiner (ADX-H-CHC)
ADX-H-CHC
UL1 UL2 UL3 UL4
DL1 DL2 DL3 DL4
UL5 UL6 UL7 UL8
DL5 DL6 DL7 DL8