Specifications

Command Set 3-47
3. 35. Set Low Alarm
@Description
Set low alarm limit value at specified analog input module.
@Syntax
@(Addr)LO(Data)<CR>
@
Command leading code.
(Addr) Address ID
LO Set low alarm limit value.
(Data) Alarm low limit value.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point.
@Response
!(Addr)<CR>
! Command is valid.
(Addr) Address ID.
@Example
User command: @06LO+100.00<CR>
Response: !06<CR>
Set low alarm limit value to +100°C to accept J-type thermocouple input
at address 06H.
(6011/D, 6012/D, 6014D)