Specifications

3-44 Command Set
3. 32. Set Digital Output
@Description
Set digital output channel at specified module.
@Syntax
@(Addr)DO(OutData)<CR>
@ Command leading code.
(Addr) Address ID
DO Set digital output
(OutData) Digital output data .(2 - characters)
00 : bit 1 is OFF, bit 0 is OFF.
01 : bit 1 is OFF, bit 0 is ON.
02 : bit 1 is ON , bit 0 is OFF
03 : bit 1 is ON , bit 0 is ON.
@Response
!(Addr)<CR>
or
?(Addr)<CR>
! Command is valid.
? Command is invalid.
(Addr) Address ID.
@Example
User command: @06DO02<CR>
Response: !06<CR>
Set the digital output channel state at address 06H, digital output
channel port 0 is OFF, port 1 is ON.
(6011/D, 6012/D, 6014D)