3. 13. Offset Calibration to each Channel
@Description
To correct the offset errors of AD converter by using the offset
calibration.
@Syntax
$(Addr)1(Channel No)<CR>
$ Command leading code
(Addr) Address ID
1 Offset calibration.
(Channel No) Channel for calibration.(1 character)0~2
@Response
!(Addr)<CR>
or
?(Addr)<CR>
! Command is valid.
? Command is invalid.
(Addr) Address ID.
@Example
User command: $0612<CR>
Response: !06<CR>
To perform the offset calibration for analog input module ND-6013
channel 2 at specified address 06 (Hex).
Note : To perform the calibration, a proper input signal should be
connected to the analog input module. Different input range
have different input voltage, detail refer chapter 5 “Calibration” .
(6013)