Specifications
Command Set 3-21
3. 12. Offset Calibration
@Description
To correct the offset errors of AD converter by using the offset
calibration.
@Syntax
$(Addr)1<CR>
$ Command leading code
(Addr) Address ID
1 Offset calibration.
@Response
!(Addr)<CR>
or
?(Addr)<CR>
! Command is valid.
? Command is invalid.
(Addr) Address ID.
@Example
User command: $061<CR>
Response: !06<CR>
To perform the offset calibration for analog input module at specified
address 06 (Hex).
Note : To perform the calibration, a proper input signal should be
connected to the analog input module. Different input range
have different input voltage, detail refer chapter 5 “Calibration” .
(6011/D, 6012/D
6014D, 6017, 6018)