Specifications

3-12 Command Set
3. 4. Read Configuration
@Description
Read the configuration of module on a specified address ID.
@Syntax
$(Addr)2<CR>
$ Command leading code
(Addr) Address ID.
2 Command code for reading configuration
@Response
!(Addr)(InputRange)(BaudRate)(DataFormat)<CR>
or
?(Addr)<CR>
!
Command is valid.
? Command is invalid.
(Addr) Address ID.
(InputRange) Current setting of analog voltage input, refers
to Table 3-1 for details.
(BaudRate) Current setting of communication baud rate,
refers to Table 3-2 for details.
(DataFormat) Current settings of checksum, integration time
and output data format, refers to Figure 3-1
for details.
@Example
User command: $302<CR>
Response: !30050600<CR>
! Command is valid.
30 Address ID.
05
Analog input range is ±2.5 V.
06 Baud rate is 9600 bps.
00 checksum is disable.
(6011/D, 6012/D, 6013
6014D, 6017, 6018)