Specifications

Command Set 3-11
Code Baudrate
03 1200 bps
04 2400 bps
05 4800 bps
06 9600 bps
07 19200 bps
08 38400 bps
09 115200 bps
Table 3-2 Baud rate setting code
Figure 3-1 Data Format Setting of Analog Input Modules
7 6 5 4 3 2 1 0
Reserved
Must to be 0
Checksum
0 : disable
1 : enable
Analog Input Data Format
00 : Engineering units
01 : % of Full Scale Range
10 : Two’s complement of hexadecimal
11 : Ohms (6013 only)
Note :
6017/6018 only support engineering
units.
6013 supports engineering units and
ohms display.