Specifications
Command Set 3-45
3. 38. Read Digital Output and Alarm Status
@Description
Read the current digital output channel values and the status of
alarm function.
@Syntax
@(Addr)DI<CR>
@
Command leading code.
(Addr)
Address ID
DI
Read digital data output and alarm status
command code.
@Response
!(Addr)(AStatus)(DoData)00<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(AStatus)
0: counter 0 alarm is disabled, counter 1
alarm is disabled.
1: counter 0 alarm is enabled, counter 1 alarm
is disabled.
2: counter 0 alarm is disabled, counter 1 alarm
is enabled.
3: counter 0 alarm is enabled, counter 1 alarm
is enabled.
(DoData)
00: DO0 is OFF, DO1 is OFF
01: DO0 is ON, DO1 is OFF
02: DO0 is OFF, DO1 is ON
03: DO0 is ON, DO1 is ON