Specifications

Command Set 3-43
3. 36. Read Alarm Limit Value of Counter 1
@Description
Read the alarm limit value of counter 1.
@Syntax
@(Addr)RA<CR>
@
Command leading code.
(Addr) Address ID (2-character)
RA
Read alarm limit value command code
@Response
!(Addr)(ArmData)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(ArmData)
The alarm limit value which consists of 8
hexadecimal digits.
@Example
User command: @30RA<CR>
Response: !300001FFFF<CR>
Item Meaning Description
@ (Leading Code) Command leading code.
30 (Addr) Address ID is 30H.
RA Read alarm limit value of counter
0.
!
Command is valid.
30
Address of counter/frequency module.
0001FFFF
131071(0x0001FFFF).