Specifications

2-2 Initialization & Installation
Default State
The NuDAM modules must be set at Default State when you want to
change the default settings, including the ID address, baud rate, check-
sum status etc. All NuDAM modules have an special pin labeled as
DEFAULT*. The module will be in Default State if the Default*
1
pin is
shorted to ground when power ON. Under this state, the default
configuration is set as following:
Address ID is 00.
Baud rate is 9600 bps.
Check-sum disable.
Watchdog timer is disable.
Therefore, the configuration of the host and the module can be easily
set identically and initializing a module will be possible no matter what
configuration is set under operating state.
Initialization Equipments
Host computer with an RS-232 port.
An installed RS-485 module (NuDAM-6520) with 9600 baud rate.
The brand new NuDAM module
Power supply (+10 V
DC
to +30 V
DC
) for NuDAM modules
Administration utility software
Note1: Never Connect the DRFAULT* pin to Vs or power source just left it
open or wired to GND.