Specifications

Initialization & Installation 2-1
2. Initialization & Installation
2. 1. Software Installation
1. If you have already installed “NuDAM Administration” then skip other
steps.
2. Backup your software diskette.
3. Insert “NuDAM Administration” disc into CD-ROM:
4. Change drive to the path of CD-ROM. For example, your drive of CD-
ROM is F:, then change the drive to F:
5. Find the setup of NuDAM Administration and run it.
6. Please follow the steps of setup program then you can successful to
install the nudism Administration.
2. 2. Initializing a Brand-New Module
Objective of Initializing a Brand-New NuDAM
All NuDAM modules, except NuDAM-6520 and NuDAM-6510, in a RS-
485 network must have an unique address ID. Every brand-new NuDAM
has a factory default setting as following:
Address ID is 01.
Baud rate is 9600 bps
Check-sum disable
Host Watchdog timer is disable
Therefore, to configure the brand-new NuDAM before using is
necessary to avoid conflicting address. The baud rate may also be
changed according to user‘s requirements.
The initialization procedures of a brand-new NuDAM are shown in the
following sections. The procedures are applicable for initializing
NuDAM-6011/D, NuDAM-6012/D, NuDAM-6013, NuDAM-6014D,
NuDAM-6017, and NuDAM-6018.