Specifications

Command Set 3-7
3. 3. Set Configuration
@Description
Configure the basic setting about address ID, baud rate, and
checksum.
@Syntax
%(OldAddr)(NewAddr)(TypeCode)(BaudRate)(CheckSumFlag)<CR>
% Command leading code. (1-character)
(OldAddr)
NuDAM module original address ID. The
default address ID of a brand new module
is 01. The value range of address ID is 00
to FF in hexadecimal. (2-character)
(NewAddr)
New address ID, if you don’t want to
change address ID, let new address ID
equals to the old one. (2-character)
(TypeCode)
Type Code represents the input mode.
(2-character)
50: counter input mode
51: frequency input mode
(BaudRate)
Communication baud rate, refer to Table
3-1 for details. (2-character)
(CheckSumFlag)
Define check-sum status and frequency
gate time, refer to Table 3-2 for details.
(2-character)
@Response
!(Addr)<CR>
or
?(Addr)<CR>
(Addr)
Address ID.
!
Command is valid.
?
Command is invalid. Invalid parameter values,
When you wanted to change the setting without
grounding the DEFAULT* pin.