Specifications

1-2 Introduction
Features of NuDAM-6080
Two 32 bit counter / frequency input channel
Two digital output channels of open collector type
5000 Vrms isolation voltage for isolated input mode
External gate control for counter input
Alarm function with alarm output
Programmable digital filter for noise rejection
Programmable threshold setting of trigger level for non-
isolated input mode
Programmable host watchdog timer for host failure protection
Internal watchdog timer for device failure protection
Easy programming by software
Easy installation and wiring
Specifications of NuDAM-6080
² Interface
Interface : RS-485, 2 wires
Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K
² Counter Input
Two independent 32 bit counters
Input frequency: 100 kHz max.
Input mode: Isolated or non-isolated
Isolated input level:
Logic level 0: +1V max.
Logic level 1: +3.5V to +30V
Isolation voltage: 5000 Vrms
Non-isolated input level (programmable threshold):
Logic level 0: 0 to +5V (default = 0.8V)
Logic level 1: 0 to +5V (default = 2.4V)
Input pulse width > 5 µsec.
Programmable digital noise filter:
4 µsec. to 1.02 msec.
Alarm comparator on each counter