Specifications

3-6 Command Set
3. 3. Set Configuration
@Description
Configure the basic setting about address ID, baud rate, and checksum.
@Syntax
%(OldAddr)(NewAddr)(TypeCode)(BaudRate)(CheckSumFlag)<CR>
%
Command leading code.
(1-character)
(OldAddr)
NuDAM module original address ID. The
default address ID of a brand new module is
01. The value range of address ID is 00 to FF
in hexadecimal. (2-character)
(NewAddr)
New address ID, if you don’t want to change
address ID, let new address ID equals to the
old one. (2-character)
(TypeCode)
Type Code is fixed 40H for Digital I/O
modules. (2-character)
(BaudRate)
Communication baud rate, refer to Table 3-1
for details. (2-character)
(CheckSumFlag)
Define check-sum status, refer to Table 3-2
for details. (2-character)
@Response
!(Addr)<CR>
or
?(Addr)<CR>
(Addr)
Address ID.
!
Command is valid.
?
Command is invalid. Invalid parameter values,
When you wanted to change the setting without
grounding the DEFAULT* pin.
Note : When you want to change the checksum or baud rate then the
DEFAULT* pin should be grounded at first.
@Example
(6050, 6052, 6053, 6054,
6056, 6058, 6060, 6063)