Initializtion & Installation 2-1
2. Initialization & Installation
2. 1. Software Installation
1. If you have already installed “NuDAM Administration” then skip
other steps.
2. Backup your software diskette.
3. Insert “NuDAM Administration” disc into CD-ROM:
4. Change drive to the path of CD-ROM. For example, your drive
of CD-ROM is F:, then change the drive to F:
5. Find the setup of NuDAM Administration and run it.
6. Please follow the steps of setup program then you can
successful to install the nudism Administration.
2. 2. Initializing a Brand-New Module
Objective of Initializing a Brand-New NuDAM
All NuDAM modules. except NuDAM-6520 and NuDAM-6510, in a RS-
485 network must have an unique address ID, however, every brand-
new NuDAM has a factory default setting as following:
• Address ID is 01.
• Baud rate is 9600 bps
• Check-sum disable
• Host Watchdog timer is disable
Therefore, to configure the brand-new NuDAM before using is
necessary, otherwise the address ID will be conflict with others modules
because the ID of new modules are identity . The baud rate may also be
changed according to user‘s requirements.
The following sections show how to initialize a brand-new module, which
is applicable for initializing NuDAM-6050, NuDAM-6052, NuDAM-6053,
NuDAM-6054, NuDAM-6056, NuDAM-6058, NuDAM-6060, and NuDAM-
6063.